(2) The color shall be clear or nominal while (ie., unfiltered or clear filtered white light).
(3) The maximum pulse duration shall be two tenths of one second (0.2 sec) with a maximum duty cycle of 40 percent. The pulse duration is defined as the time interval between initial and final points of 10 percent of maximum signal.
(4) The intensity shall be a minimum of 75 candela.
(6) The appliance shall be placed 80 in (2030 mm) above the highest floor level within the space or 6 in (152 mm) below the ceiling, whichever is lower.
(7) In general, no place in any room or space required to have a visual signal appliance shall be more than 50 ft (15 m) from the signal (in the horizontal plane). In large rooms and spaces exceeding 100 ft (30 m) across, without obstructions 6 ft (2 m) above the finish floor, such as auditoriums, devices may be placed around the perimeter, spaced a maximum 100 ft (30 m) apart, in lieu of suspending appliances from the celling.
(8) No place in common corridors or hallways in which visual alarm signaling appliances are required shall be more than 50 ft (15 m) from the signal.
(“ Standards for Accessible Design”, 28 CFR 36 Appendix D)